Kinerja Sistem Pembumian Tower Telekomunikasi di Manokwari Berdasarkan Resistansi Pembumian dan Resistivitas Tanah
Grounding System Performance of a Telecommunication Tower in Manokwari Based on Earth Resistance and Soil Resistivity
DOI:
https://doi.org/10.30862/9hbbfv47Keywords:
Earth resistance, Fall of Potential, Wenner four-point, Two-layer soil model, Telecommunication towerAbstract
Grounding systems on telecommunication towers discharge fault and lightning currents safely to earth and protect sensitive equipment. This study evaluated the grounding system of a tower owned by PT. Dayamitra Telekomunikasi in Amban, Manokwari, West Papua. Earth resistance was measured using the Fall of Potential method with a 20 m distance between the tested electrode and the current electrode, and the potential electrode was placed at 52% (10.4 m), 62% (12.4 m), and 72% (14.4 m) following IEEE Std 81-2012. Soil resistivity was measured using the Wenner four-point method at electrode spacings of 2 m and 3.1 m along five spans and interpreted with a two-layer soil model. The earth resistance at the 62% reference point was 19.62 Ω in the first measurement and 15.98 Ω in the second, so the system met neither the 5 Ω limit nor the stricter criterion of less than 1 Ω. Soil resistivity ranged from 17.2 to 91.8 Ωm, indicating non-homogeneous soil, and the reflection factor was −0.100. Improvements, such as adding parallel ground rods, are required to lower the resistance and improve the reliability of lightning protection.